Schneider Electric 9070 Personal Lift User Manual


 
56
© 1999–2005 Schneider Electric All Rights Reserved 08/2005
Industrial Control Transformers
Application
Example of a typical application
OEM customer base source voltages in United States: 208, 240, or 480 volts (From past shipments
480 is 65% of the business, 208 is 20%, and 240 is 10%)
5% of business goes into Canada and needs 600 volts; customer always knows when equipment
goes to Canada.
Load requirement is for a 500VA transformer, load is 120 volt control
For this customer, Schneider Electric has the following solutions:
Solution 1
Three standard units with interchangeable dimensions
9070T500D1—240 x 480 to 120; handles 75% of business. For details, see the tables on page 8.
9070T500D3—208 to 120; handles 20% of business. For details, see the tables on page 9.
9070T500D5—600 to 120; handles 5% of business. For details, see the tables on page 9.
Solution 2
Two MultiTap units with interchangeable dimensions
9070T500D20—208/230/460 to 115; handles 95% of business {US Voltage Code}. For details, see
the tables on page 10.
9070T500D32—230/460/575 to 95/115; handles 5% of business {North American Voltage Code};
covers 460 and 575 Canadian sources. For details, see the tables on page 11.
Solution 3
One Universal Control Transformer
9070T500D50—240/416/480/600 to 99/120/130. For details, see the tables on page 12.