Schneider Electric 9070 Personal Lift User Manual


 
Industrial Control Transformers
Multiple Secondary
21
08/2005
© 1999–2005 Schneider Electric All Rights Reserved
Type T Units with Dual 24/120 Volt Secondary (Tapped Units)
Voltage and Connection Options
Voltage
Code
Voltages Connections
Primary Secondary Primary Secondary
D65
200/220/440
208/230/460
217/240/480
23/110
24/115
25/120
200 or 208 or 217:Connect to H1 and H2
220 or 230 or 240:Connect to H1 and H3
440 or 460 or 480:Connect to H1 and H4
23 or 24 or 25: Connect to X1 and X2
110 or 115 or 120:Connect to X1 and X3
X3 X2 X1
H1 H3 H4H2
Dimensions
VA
Catalog
Number
Fig.
Acc.
Key
ABCEF Slots
115
Only
Max
VA
24
Only
Max
VA
Simultaneous
Loading Max
UL VA
UL CE IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
UL UL 115V 24V
50 50 9070T50D65 1 II 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 50 50
Any
combination
that does not
exceed
Primary Max
VA
For example,
T350
200VA (120V)
150VA (24V)
75 75 9070T75D65 1 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 75 75
100 100 9070T100D65 1 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 100 100
150 150 9070T150D65 1 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 150 150
200 200 9070T200D65 2 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 200 200
250 160 9070T250D65 2 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 250 250
300 200 9070T300D65 2 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 .20 x .38 5 x 10 300 300
350 250 9070T350D65 2 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 350 350
500 300 9070T500D65 2 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 500 500
D
A
B
F
E
C
Figure 2Figure 1
C
B
D
A
E
F