Schneider Electric 9070 Personal Lift User Manual


 
Industrial Control Transformers
Type EO Transformers
31
08/2005
© 1999–2005 Schneider Electric All Rights Reserved
24 Volt Control Secondary
Voltage and Connection Options
Voltage
Code
Voltages Connections
Primary Secondary Primary Secondary
D2 240 x 480
24
240 or 120 or 115 or 230:Connect to H1 and H4
Jumper H1 with H3
Jumper H2 with H4
480 or 240 or 230 or 460:Connect to H1 and H4
Jumper H2 with H3
Connect to X1 and X2
D23 120 x 240
D89 115 x 230
D92 230 x 460
H1
X2 X1
H2H3 H4
Dimensions
VA
Catalog
Number
1
Fig.
ABCEF Slots
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
25 9070EO17t 6 3.31 84 3.00 76 2.50 64 1.75 44 2.50 64 0.20 x 0.38 5 x 10
50 9070EO1t 6 3.31 84 3.00 76 2.50 64 2.00 51 2.50 64 0.20 x 0.38 5 x 10
75 9070EO18t 6 3.78 96 3.38 86 2.81 71 2.19 56 2.81 71 0.20 x 0.38 5 x 10
100 9070EO2t 6 3.78 96 3.38 86 2.81 71 2.38 60 2.81 71 0.20 x 0.38 5 x 10
150 9070EO3t 6 4.44 113 3.75 95 3.13 80 2.88 73 3.13 80 0.20 x 0.38 5 x 10
200 9070EO19t 6 4.81 122 4.50 114 3.75 95 2.5 63 3.75 95 0.20 x 0.38 5 x 10
250 9070EO15t 6 5.19 132 4.50 114 3.75 95 2.88 73 3.75 95 0.20 x 0.38 5 x 10
300 9070EO04t 6 5.56 141 4.50 114 3.75 95 3.81 97 3.75 95 0.20 x 0.38 5 x 10
350 9070EO16t 6 6.19 157 4.50 114 3.75 95 3.81 97 3.75 95 0.20 x 0.38 5 x 10
500 9070EO51t 6 6.56 167 5.25 133 4.38 111 3.81 97 4.38 111 0.28 x 0.56 7 x 14
750 9070EO61t 6 7.94 202 5.25 133 4.38 111 5.13 130 4.38 111 0.28 x 0.56 7 x 14
1000 9070EO71t 6 7.94 202 6.00 152 5.00 127 4.75 121 5.00 127 0.28 x 0.56 7 x 14
1500 9070EO81t 6 8.59 218 7.06 179 6.03 153 5.88 149 5.81 148 0.44 x 0.69 11 x 18
1
Complete the catalog number by replacing the t with the correct Voltage Code from the “Voltage and Connection Options” table above.
Figure 6