Schneider Electric 9070 Personal Lift User Manual


 
Industrial Control Transformers
Type T MultiTap Transformers
11
08/2005
© 1999–2005 Schneider Electric All Rights Reserved
120 Volt Secondary
Voltage and Connection Options
Voltage
Code
Voltages Connections
Primary Secondary Primary Secondary
D18 208/277/380 95/115
208: Connect to H1 and H2
277: Connect to H1 and H3
380: Connect to H1 and H4
95: Connect to X1 and X2
115: Connect to X1 and X3
D32
220/440/550
230/460/575
240/480/600
90/110
95/115
100/120
220 or 230 or 240: Connect to H1 and H2
440 or 460 or 480: Connect to H1 and H3
550 or 575 or 660: Connect to H1 and H4
90 or 95 or 100: Connect to X1 and X2
110 or 115 or 120: Connect to X1 and X3
D95
190/220/440
200/230/460
208/240/480
110
115
120
190 or 200 or 208: Connect to H1 and H2
220 or 230 or 240: Connect to H1 and H3
440 or 460 or 480: Connect to H1 and H4
110 or 115 or 120: Connect to X1 and X2
H1
X3 X2 X1
H3 H4H2
H1
X2 X1
H3 H4H2
Dimensions
VA
Catalog
Number
1
Figure
Acc.
Key
ABCEF Slots
UL CE IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
25 25 9070T25t 1 II 3.09793.00762.58662.00512.50640.20 x 0.385 x 10
50 50 9070T50t 1 II 3.34853.38862.89732.38612.81710.20 x 0.485 x 12
75 75 9070T75D32 1 II 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12
75 75 9070T75t
2
1 II 3.59913.75953.20812.88733.13800.20 x 0.385 x 10
100 100 9070T100t 1 II 3.59913.75953.20812.88733.13800.20 x 0.385 x 10
150 150 9070T150D32 2 II 4.70 119 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10
150 150 9070T150t
2
1 II 3.59913.75953.20812.88733.13800.20 x 0.385 x 10
200 200 9070T200t 2 II 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 0.20 x 0.38 5 x 10
250 160 9070T250D32 2 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 0.20 x 0.38 5 x 10
250 160 9070T250t
2
2 II 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 0.20 x 0.38 5 x 10
300 200 9070T300D32 2 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 0.20 x 0.38 5 x 10
300 200 9070T300t
2
2 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 0.20 x 0.38 5 x 10
350 250 9070T350t 2 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 0.20 x 0.38 5 x 10
500 300 9070T500t 2 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 0.28 x 0.56 7 x 14
750 500 9070T750t 2 II 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111 0.28 x 0.56 7 x 14
1000 630 9070T1000t 2 II 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148 0.28 x 0.56 7 x 14
1500 1000 9070T1500t 2 II 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148 0.28 x 0.56 7 x 14
2000 1500 9070T2000t 2 II 6.38 162 9.00 229 7.63 194 4.63 118 7.63 194 0.44 x 1.13 11 x 29
3000 2000 9070T3000t 3 II 9.15 232 9.00 229 8.75 222 6.56 167 7.63 194 0.44 x 1.13 11 x 29
1
Complete the catalog number by replacing the t with the correct Voltage Code from the “Voltage and Connection Options” table above.
2
Complete the catalog number by replacing the t with Voltage Code D18 or D95 from the “Voltage and Connection Options” table above.
Figure 3
B
D
A
E
F
C
D
A
B
F
E
C
Figure 2Figure 1
C
B
D
A
E
F