Schneider Electric 9070 Personal Lift User Manual


 
Industrial Control Transformers
Type T Transformers with Dual Secondary
13
08/2005
© 1999–2005 Schneider Electric All Rights Reserved
120/240 Volt Secondary
-
Voltage and Connection Options
Voltage
Code
Voltages Connections
Primary Secondary Primary Secondary
D31
220 x 440
230 x 460
240 x 480
110/220
115/230
120/240
220 or 230 or 240:Connect to H1 and H4
Jumper H1 with H3
Jumper H2 with H4
440 or 460 or 480:Connect to H1 and H4
Jumper H2 with H3
110 or 115 or 120:Connect to X1 and X4
Jumper X1 with X3
Jumper X2 with X4
220 or 230 or 240:Connect to X1 and X4
Jumper X2 with X3
D55
110 x 220
115 x 230
120 x 240
110 x 220
115 x 230
120 x 240
110 or 115 or 120:Connect to H1 and H4
Jumper H1 with H3
Jumper H2 with H4
220 or 230 or 240:Connect to H1 and H4
Jumper H2 with H3
110 or 115 or 120:Connect to X1 and X4
Jumper X1 with X3
Jumper X2 with X4
220 or 230 or 240:Connect to X1 and X4
Jumper X2 with X3
H1
X4 X2 X3
H3 H2
X1
H4
Dimensions
VA
Catalog
Number
1
Figure
Acc.
Key
ABCEF Slots
UL CE IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
25 25 9070T25t 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 0.20 x 0.38 5 x 10
50 50 9070T50t 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 0.20 x 0.38 5 x 10
75 75 9070T75t 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12
100 100 9070T100t 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12
150 150 9070T150t 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10
200 200 9070T200t 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10
250 160 9070T250t 2 I 5.301353.75953.21822.88733.13800.20 x 0.385 x 10
300 200 9070T300t 2 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 0.20 x 0.38 5 x 10
350 250 9070T350t 2 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 0.20 x 0.38 5 x 10
500 300 9070T500t 2 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 0.20 x 0.38 5 x 10
750 500 9070T750t 2 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 0.28 x 0.56 7 x 14
1000 630 9070T1000t 2 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111 0.28 x 0.56 7 x 14
1500 1000 9070T1500t 2 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148 0.28 x 0.56 7 x 14
2000 1500 9070T2000t 2 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148 0.28 x 0.56 7 x 14
3000 2000 9070T3000t 2 I 6.38 162 9.00 229 7.63 194 4.63 118 7.63 194 0.44 x 1.13 11 x 29
5000 3000 9070T5000t 2 I 8.31 211 9.00 229 7.63 194 6.56 167 7.63 194 0.44 x 1.13 11 x 29
1
Complete the catalog number by replacing the t with the correct Voltage Code from the “Voltage and Connection Options” table above.
D
A
B
F
E
C
Figure 2Figure 1
C
B
D
A
E
F