Industrial Control Transformers
Fuse Protection
Applications for Line-to-Line Primary protection and Line-to-Line Secondary protection,
Example would be 480 to 120/240 (Voltage Code D31)
Available as field installed only for 9070 Type T
Must order one 9070FB2A(B) - Primary
Must order one 9070S22A(B) - Secondary
Application for Line-to-Line Primary protection and Line-to-Neutral Secondary protection
Example would be 480 to 120 (Voltage Code D1)
Available as factory and field installed
Factory installed - 9070 Type TF or 9070 Type EOF
Field installed - 9070 Type T: 9070FB3A or 9070FB3B
Application for Line-to-Line Primary protection and no secondary protection
Example would be 480 to 24 (voltage Code D2)
Available as factory and field installed
Factory installed - 9070 Type TF with R02 suffix or 9070 Type EOF with R02 suffix
Field installed - 9070 Type T: 9070FB2A or 9070FB2B
Application for no Primary protection and Line-to-Line Secondary
Example would be 480 to 120/240 (voltage Code D31)
Primary protection done else where in the circuit
Factory installed - 9070 Type T or 9070 Type EO with S22 Suffix
Field installed - 9070 Type T: 9070S22A or 9070S22B
Application for Line-to-Neutral Primary and Line-to-Line Secondary
Example would be 277 to 120/240
Factory installed - 9070 Type TF with R12 suffix or 9070 Type EOF with R12 suffix
Field installed - 9070 Type T: 9070R12A or 9070R12B