Schneider Electric 9070 Personal Lift User Manual


 
Industrial Control Transformers
Multiple Secondary
22
© 1999–2005 Schneider Electric All Rights Reserved 08/2005
Type T Units with Dual 24/120 Volt Secondary (Separate Windings)
Voltage and Connection Options
Voltage
Code
Voltages Connections
Primary Secondary Primary Secondary
D114
220 x 440
230 x 460
240 x 480
23/110
24/115
25/120
220/230/240:Connect to H1 and H4
Jumper H1 with H3
Jumper H2 with H4
440/460/480:Connect to H1 and H4
Jumper H2 with H3
23/24/25: Connect to X1 and X2
110/115/120:Connect to X3 and X4
H1
H3 H2
H4
X4 X3 X2 X1
Dimensions
VA
Catalog
Number
Fig.
Acc.
Key
ABCEF Slots
115
Only
Max
VA
24
Only
Max
VA
Simultaneous
Loading Max
UL VA
UL CE IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
IN
mm
UL UL 115V 24V
50 50 9070T50D114 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 50 50
Any
combination
that does not
exceed
Primary Max
VA
For example,
T350
200VA (120V)
150VA (24V)
75 75 9070T75D114 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 75 75
100 100 9070T100D114 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 100 100
150 150 9070T150D114 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 150 150
200 200 9070T200D114 2 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 200 200
250 160 9070T250D114 2 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 250 250
300 200 9070T300D114 2 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 300 300
350 250 9070T350D114 2 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 .20 x .38 5 x 10 350 350
500 300 9070T500D114 2 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 500 500
D
A
B
F
E
C
Figure 2Figure 1
C
B
D
A
E
F