5.1 Q Series Safety Relay Module
5.1.4 Mounting/removal
5 - 6
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
SETTINGS AND
PROCEDURES BEFORE
OPERATION
6
TROUBLESHOOTINGAPPENDIX
5.1.4 Mounting/removal
For mounting/removing the Q series safety relay module on/from the base unit, refer to the
QCPU User's Manual (Hardware Design, Maintenance and Inspection) together.
When installing a programmable controller to a control panel or similar, fully consider its
operability, maintainability, and environmental resistance.
(1) Installation position
Keep the clearances shown below between the top/bottom faces of the modules and
the control panel or other parts so that good ventilation is ensured and the modules
can be easily replaced.
* 1: A clearance required when the wiring duct is 50mm or less in height A 40mm or more clearance is
required when the wiring duct is longer.
Figure 5.3 Installation position
*1
Ceiling of the control panel,
wiring duct or any other parts
5mm or more 5mm or more
30mm or more
30mm or more
20mm
or more
Programmable
controller
DoorControl
panel