3 - 1
3.1 General Specifications
3
SPECIFICATIONS
CHAPTER 3 SPECIFICATIONS
3.1 General Specifications
Table 3.1 shows the general specifications of the safety relay module.
* 1: This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery within the
premises.
Category III applies to devices in fixed equipment such as a switching device and industrial
machine.
The surge voltage withstand level of equipment for up to the rated voltage of 300V is 4000V.
* 2: This index indicates the degree to which a conductive material is generated in the environment
where the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. However, temporary conductivity
may be produced due to incidental condensation.
* 3: The storage ambient temperature is -20 to 75 if the system includes any CC-Link safety relay
modules or extension safety relay modules.
* 4: Do not use or store the programmable controller under pressure higher than the atmospheric
pressure of altitude 0m.
Doing so may cause a malfunction.
When using the programmable controller under pressure, please contact your local Mitsubishi
office.
Table 3.1 General specifications
Item Specifications
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-25 to 75
*3
Operating ambient humidity
30 to 85%RH, non-condensing
Storage ambient humidity
Vibration resistance
JIS B 3502,
IEC 61131-2
compliant
Frequency
Constant
acceleration
Half
amplitude
Sweep count
Under
intermittent
vibration
5 to 8.4Hz -
3.5mm
(0.14inch)
10 times each
in X, Y, Z
directions
8.4 to 150Hz
9.8m/s
2
-
Under
continuous
vibration
5 to 8.4Hz -
1.75mm
(0.069inch)
-
8.4 to 150Hz
4.9m/s
2
-
Shock resistance
JIS B 3502, IEC 61131-2 compliant
(147m/s
2
, duration of action 11ms, 3 times each in 3 directions X, Y, Z by sine half-wave
pulse)
Operating ambience No corrosive gases
Operating altitude
*4
0 to 2000m
Installation location Inside of control panel of IP standard 54 or more
Overvoltage category
*1
III or less
Pollution degree
*2
2 or less
Equipment class Class I