![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/4/a1/4a1bb5e3-fbdb-4eff-9c71-f976df3bde1c/4a1bb5e3-fbdb-4eff-9c71-f976df3bde1c-bg4e.png)
ADCP-75-210 • Issue 1 • March 2007
Page 66
© 2007, ADC Telecommunications, Inc.
7. Using cable 1001475P001, connect the PA CTL1/3 connector on the RUC module to
either of the following as appropriate:
– CNTL port on PAA1 if RUC module is in slot A2
– CNTL port on PAA3 if RUC module is in slot A5
8. Using cable 1001475P001, connect the CTL 2/4 connector on the RUC module to either of
the following as appropriate:
– CNTL port on PAA2 if RUC module is in slot A2
– CNTL port on PAA4 if RUC module is in slot A5
4.2 Installing cPCI Chassis Air Baffles
The air baffles for the RAN chassis are used in all empty chassis slots. This is done to maintain
airflow around the chassis modules.
Use the following procedure to install air baffles:
1. Identify designated RAN Chassis cPCI slot for the cPCI air baffle.
2. Insert air baffle into designated slot on chassis and tighten screws.
4.3 Installing a Rectifier Module
To install a rectifier module, use the following procedure (Figure 47):
1. Connect cables following Section 22 on Page 66.
2. Slide the rectifier into the rectifier compartment.
3. Turn the gravity latch down to lock the rectifier in place.
Note: For a description of the rectifier including function, controls, and indicators, refer
to Section 1.8 on Page 23. For a RAN chassis interconnection diagram, refer to Figure 40
on Page 58.
Table 22. Rectifier Ports and Connections
RECTIFIER PORT CONNECTS TO USING CABLE COMMENTS
L1, L2, L3 EMI Line Filter
F-L1, F-L2
1001473P001 Connect black wire to F-L1 (on EMI Line Filter); connect
brown wire to FL-2
RECT GND GND Stud 1001473P001 Connect to cabinet ground stud
+BAT, -BAT Anderson con-
nector
1001477P001 Connect to Anderson connector in battery compartment;
connect black wire to 0V (+BAT) and blue wire to -BAT
OV OUT,
-OV OUT
temp sensor,
circuit break-
ers REC+ and
REC-
1001477P001
1001469P001
1001470P001
Place temperature sensor in battery compartment; connect
1001477P001 black wire to OV OUT and blue wire to -
OV OUT; connect 1001469P001 from rectifier OV OUT
to circuit breaker POS; connect 1001470P001 from recti-
fier -OV OUT to circuit breaker NEG