(c) "PLC Side Device"
Set auto refresh target devices. The following devices can be set.
There are two auto refresh device range setting methods.
*1
Setting device ranges sequentially from the start device number of CPU No.1
Setting device ranges for each CPU module freely
*1 Auto refresh devices of the following QCPUs can only be set sequentially from the start device of CPU No.1.
In addition, when GX Developer version 8.22Y or earlier is used, auto refresh devices shall only be set sequentially from
the start device of CPU No.1.
Each CPU module uses the device ranges corresponding to the points set for the module from the specified
start device number as the auto refresh target ranges. Set device numbers so that the necessary amount of
send points can be secured.
Device Restriction
Data register (D),
Link register (W),
File register (R, ZR)
Link relay (B),
Internal relay (M),
Output (Y)
Specify 0 or multiples of 16 for the start number.
•Basic model QCPU
• High Performance model QCPU with a serial number (first five digits) of "07031" or earlier
• Process CPU
Set Starting Devices for each PLC:
Device ranges are set for each CPU
module freely.
Set Starting Devices for each PLC:
Device ranges are set sequentially from
the start device number of CPU No.1.