Mitsubishi Electronics Q06PHCPU Sleep Apnea Machine User Manual


 
104
CHAPTER 5 ACCESS BETWEEN CPU MODULES
AND OTHER MODULES
This chapter describes the access between CPU modules and other modules (I/O modules and intelligent function
modules).
5.1 Access to Controlled Modules
In a multiple CPU system, CPU modules access I/O modules and intelligent function modules in the same way as in a
single CPU system. (CPU modules refresh input (X) and output (Y) data, and read/write data from/to the buffer
memory of intelligent function modules.)
5.2 Access to Non-controlled Modules
Access to non-controlled modules is restricted as shown below.
: Accessible ×: Inaccessible
The on/off data of the I/O modules, I/O combined modules, and intelligent function modules controlled by other CPU
modules can be used as an interlock of the host CPU module or to check the status of output to external devices
controlled by other CPU modules.
The on/off status of input (X) and output (Y) can be read by setting "I/O Sharing When Using Multiple CPUs" in PLC
parameter. (The on/off status cannot be written to the devices.)
Data in the buffer memory of intelligent function modules can be read regardless of the "I/O Sharing When Using Multiple
CPUs" setting. (The data cannot be written to the buffer memory.)
Access target
"I/O Sharing When Using Multiple CPUs" in PLC parameter
Disabled (not checked) Enabled (checked)
Input (X) ×
Output (Y)
Read ×
Write × ×
Buffer memory of an intelligent
function module
Read
Write × ×