KitchenAid W101871170D Oxygen Equipment User Manual


 
8
INSTALLATION INSTRUCTIONS
INTERIOR-MOUNTED VENT MOTOR
Venting Methods
Determine which venting method is best for your application.
Vent system can terminate either through the wall or floor.
Island location
NOTE: For island locations, the blower motor can be mounted for
right, left, or rear venting if needed for your application. Most
island applications would still require the venting to be directed
down through the floor.
Built-in cabinet locations
Island Location
Vent system installed under a concrete slab using PVC
sewer pipe.
Front (Standard) Mounted Blower Motor
Rear Mounted Blower Motor
Calculating Vent System Length
It is recommended that you use round vent instead of rectangular
vent, especially if elbows are required. If rectangular vent is
required, it should be transitioned to 6" (25.4 cm) round vent as
soon as possible.
Front (standard) mounted
blower motor
Rear mounted blower motor
A. Down vent
A.Down vent
B. Rear vent
C. Left vent
D. Right vent
A
A
B
C
D
A
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round metal vent
F. 6" (15.2 cm) round PVC coupling
G.Concrete slab
H. 6" (15.2 cm) round PVC sewer pipe
I. 6" (15.2 cm) round 90° PVC sewer pipe elbow
J.Tightly pack gravel or sand completely around pipe.
K. 6" (15.2 cm) round 90° PVC sewer pipe elbow
L. 6" (15.2 cm) round PVC coupling
M. 12" (30.5 cm) minimum
A
B
C
D
E
F
G
H
I
J
K
L
M
A
B
C
D
E
F
G
H
I
J
K
L
M