ANSI X3.28/SRIO DPA
CONFIGURATION GUIDE
GE Energy Services
Restricted A071-0CG-2.02-2
Full
19
Mapped DI point not Found. Check config
Cause:
• One of the mapped digital input points could not be located in the SPABUS configuration.
Remedy:
• Ensure none of the Item Table Offsets in A071DIMP are greater than the number of records
in the SPABUS item configuration table, A070ITEM.
• Ensure all of the Item Table Offsets in A071DIMP refer only to records in the SPABUS item
configuration table, A070ITEM, of type DI, PD, or Spare (-1).
Mapped DO point not Found. Check config
Cause:
• One of the mapped digital output points could not be located in the SPABUS configuration.
Remedy:
• Ensure none of the Item Table Offsets in A071DOMP are greater than the number of records
in the SPABUS item configuration table, A070ITEM.
• Ensure all of the Item Table Offsets in A071DOMP refer only to records in the SPABUS
item configuration table, A070ITEM, of type DO or Spare (1-).
Mapped EV point not Found. Check config
Cause:
• One of the mapped event data points could not be located in the SPABUS configuration.
Remedy:
• Ensure none of the Item Table Offsets in A071EVMP are greater than the number of records
in the SPABUS item configuration table, A070ITEM.
• Ensure all of the Item Table Offsets in A071EVMP refer only to records in the SPABUS
item configuration table, A070ITEM, of type EV or Spare (-1).
Missing Configuration ... Deleting
Cause:
• The system was unable to locate the main configuration table for the ANSI X3.28/SRIO
DPA.
Remedy:
• Ensure the main configuration table, A071MAIN, exists in the configuration and is
comprised of a single record.