Full
Invalid source number
Cause:
The configured master station address is invalid.
Remedy:
Ensure the configured Master Address in A071MAIN is not the broadcast address (255).
Invalid SYS offset configured
Cause:
The configured system partition offset is invalid.
Remedy:
Ensure the configured Sys Offset in A071MAIN is a positive value.
Ensure the configured Sys Offset is less than the Obj Offset.
Invalid TM offset configured
Cause:
The configured time partition offset is invalid.
Remedy:
Ensure the configured TM Offset in A071MAIN is a positive value.
Ensure the configured TM Offset is less than the EVNT Offset.
Mapped AI point not Found. Check config
Cause:
One of the mapped analog input points could not be located in the SPABUS configuration.
Remedy:
Ensure none of the Item Table Offsets in A071AIMP are greater than the number of records
in the SPABUS item configuration table, A070ITEM.
Ensure all of the Item Table Offsets in A071AIMP refer only to records in the SPABUS item
configuration table, A070ITEM, of type AI, PI, or Spare (-1).
Mapped AO point not Found. Check config
Cause:
One of the mapped analog output points could not be located in the SPABUS configuration.
Remedy:
Ensure none of the Item Table Offsets in A071AOMP are greater than the number of records
in the SPABUS item configuration table, A070ITEM.
Ensure all of the Item Table Offsets in A071AOMP refer only to records in the SPABUS
item configuration table, A070ITEM, of type AO or Spare (-1).