GE Energy Services
ANSI X3.28/SRIO DPA
CONFIGURATION GUIDE
A071-0CG-2.02-2 Restricted
18
Full
Invalid source number
Cause:
• The configured master station address is invalid.
Remedy:
• Ensure the configured Master Address in A071MAIN is not the broadcast address (255).
Invalid SYS offset configured
Cause:
• The configured system partition offset is invalid.
Remedy:
• Ensure the configured Sys Offset in A071MAIN is a positive value.
• Ensure the configured Sys Offset is less than the Obj Offset.
Invalid TM offset configured
Cause:
• The configured time partition offset is invalid.
Remedy:
• Ensure the configured TM Offset in A071MAIN is a positive value.
• Ensure the configured TM Offset is less than the EVNT Offset.
Mapped AI point not Found. Check config
Cause:
• One of the mapped analog input points could not be located in the SPABUS configuration.
Remedy:
• Ensure none of the Item Table Offsets in A071AIMP are greater than the number of records
in the SPABUS item configuration table, A070ITEM.
• Ensure all of the Item Table Offsets in A071AIMP refer only to records in the SPABUS item
configuration table, A070ITEM, of type AI, PI, or Spare (-1).
Mapped AO point not Found. Check config
Cause:
• One of the mapped analog output points could not be located in the SPABUS configuration.
Remedy:
• Ensure none of the Item Table Offsets in A071AOMP are greater than the number of records
in the SPABUS item configuration table, A070ITEM.
• Ensure all of the Item Table Offsets in A071AOMP refer only to records in the SPABUS
item configuration table, A070ITEM, of type AO or Spare (-1).