Emerson Process Management 3051 Pacemaker User Manual


 
Quick Start Guide
13
February 2015
Note
See Figure 10 on page 15 to confirm External Button Functionality.
Figure 9. LOI Menu
Switch HART revision mode
If the HART configuration tool is not capable of communicating with HART
Revision 7, the 3051 will load a generic menu with limited capability. The
following procedures will switch the HART revision mode from the generic menu:
1. Manual Setup > Device Information > Identification > Message
a. To change to HART Revision 5, Enter: “HART5” in the Message field.
b. To change to HART Revision 7, Enter: “HART7” in the Message field.
Note
See Table 3 on page 11 to change HART revision when the correct Device Driver is
loaded.
Table 4. LOI Button Operation
Button
Left
No SCROLL
Right
Yes ENTER
Assign PV
HART Revision