Step 5: Verify configuration
Verify the configuration using any HART capable configuration tool or Local
Operator Interface (LOI) - option code M4. Configuration instructions for a Field
Communicator and LOI are included in this step. See Rosemount 3051 reference
manual (00809-0100-4007) for configuration instructions using AMS
®
Device
Manager.
Verifying configuration with a Field Communicator
A Rosemount 3051 DD must be installed on the Field Communicator to verify
configuration. Fast Key sequences for the latest DD are shown in Table 3 on page
11. For Fast Key sequences using legacy DD's, contact your local Emerson Process
Management representative.
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit
www.fieldcommunicator.com for information on updating the DD Library.
1. Verify device configuration using the fast key sequences in Ta bl e 3 .
a. A check () indicates the basic configuration parameters. At minimum,
these parameters should be verified as part of configuration and startup.
b. A (7) indicates availability only in HART revision 7 mode.
Table 3. Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence
Function
Fast Key sequence
HART 7 HART 5
Alarm and Saturation Levels
2, 2, 2, 5, 7 2, 2, 2, 5, 7
Damping
2, 2, 1, 1, 5 2, 2, 1, 1, 5
Range Values
2, 2, 2 2, 2, 2
Ta g
2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer Function
2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units
2, 2, 1, 1, 4 2, 2, 1, 1, 4
Burst Mode
2, 2, 5, 3 2, 2, 5, 3
Custom Display Configuration
2, 2, 4 2, 2, 4
Date
2, 2, 7, 1, 4 2, 2, 7, 1, 3
Descriptor
2, 2, 7, 1, 5 2, 2, 7, 1, 4
Digital to Analog Trim (4 - 20 mA Output)
3, 4, 2 3, 4, 2
Disable Configuration Buttons
2, 2, 6, 3 2, 2, 6, 3
Rerange with Keypad
2, 2, 2, 1 2, 2, 2, 1
Loop Test
3, 5, 1 3, 5, 1