2.2 Safety Data
Type numbers MSP900SH-A/** MSP900SH-U/**
Certificate numbers ATEX BAS01ATEX1061X FM 3021193
CSA 1352094X CSA 1352094X
ATEX Coding
(EU Directive 94/9/EC) II I G
Cenelec Coding EEx ia IIC T4 (-40°C<
Ta<60°C)
EEx ia IIC T6 (-40°C<
Ta<55°C)
CSA Coding Ex ia IIC T4 (-40°C<Ta<60°C) Ex ia IIC T4 (-40°C<Ta<60°C)
Ex ia IIC T6 (-40°C<
Ta<55°C) Ex ia IIC T6 (-40°C<Ta<55°C)
FM Coding IS/I/1/ABCD T6 Ta = 55°C
T4 Ta = 60°C
IS/I/0/AEx ia IIC T6 Ta = 55°C
T4 Ta = 60°C
Safety parameters
Ui 30 V Ui (Vmax) 30 V
Ii 120mA Ii (lmax) 120mA
Pi 0.82W Pi 0.82W
Li 27mH Li 27mH
Ci 5nF Ci 5nF
2.3 Pressure Equipment Directive
The MSP900SH transmitter does not enclose a pressurised volume and therefore is a component and outside the scope of the
Pressure Equipment Directive 97/ 23/EC.
Accordingly, the Declaration of Conformity for the MSP900SH does not list the Pressure Equipment Directive.
2.4 Specifications
Materials of construction:
Body Material UPVC (stabilised)
Cable sealant Epoxy adhesive
Locknut Nylon
Bracket 316 Stainless Steel
Cable PVC sheathed two core shielded cable
Electrical
Supply voltage
Transmitter in Non Hazardous area: 12-40V dc
Transmitter in Hazardous area: 12-30V dc
Output 4-20mA
Communications HART Digital communications (Rev. 5)
Earthing None required
Cable size Overall diameter 4mm, two cores each 0.22 mm
2
Cable length 3m, 20m or 50m.
Cable resistance 0.1 Ohm per metre length.
Operating
Range 0.3 to 12m
Temperature
Ambient -40°C to +60°C
Wetside -40°C to +60°C
Pressure 0 bar to 3.0 bar
(restricted to 0 - 1.0 bar for use in Canada)