Large Dehumidifying Dryers Operation 36
5-2 Dryer Operation Procedures
Controller Operation (Without Optional Alarm Horn & Reset Button)
1. Turn the disconnect on the control panel to the ON position. Power is applied to the
voltage line fuses, line side of the control power switch and the temperature
controller.
2. Turn the control power switch to the ON position. Power is applied to the
programmable relay and dew point controller. The valve will move to the start
position as follows:
a. The bed switch valve motor rotates until the cam switch makes 2 transitions.
b. If the cam switch does not make a transition within 10 seconds, a valve
motor fault is generated. “VM” is displayed on the relay screen, the alarm
light is activated. The valve motor, heaters, and blower shut off.
To restart the dryer, cycle control power to deactivate the alarm light and
restart the valve motor sequence.
Note: The relay screen which contains the Alarm Display Messages is
located inside the controller enclosure. For a list of Alarm Display
Messages, see Page 39.
WARNING! Do not attempt to check the Alarms on the Controller located within the
unit enclosure unless you are a qualified electrician!
c. The valve will normally complete one full cycle (revolution).
If the drying process shuts down due to an alarm, the dryer has been setup to
have the following operational features:
• The bed in process at power-down will remain in process.
• The bed in regeneration at power-down will remain in regeneration.
• The regeneration timing cycle will restart from the beginning.
3. Once the control power is on and no fault conditions exist, turning the OFF-ON-
START switch to the START position will start the dryer as follows:
a. The process heater is turned on and controlled by the E5CN controller.
b. The process & regen blowers are started.
c. The regen heater is turned on and the regeneration timing sequence is
initiated. The regen heater is controlled by the E5CN controller. For default
timing settings for regeneration, see the table below.
4. If either the left or right bed safety temperature switch opens, a regen heater fault is
generated. “RS” is displayed on the relay screen. The alarm light is activated. The
process heater, regen heater, and process/regen blowers are turned off.
Turn the OFF-ON-START switch to the START position to deactivate the alarm
light and restart the dryer. If either switch is still open, the dryer will not restart.