Sterling 822.00292.00 Hair Dryer User Manual


 
Large Dehumidifying Dryers Controls 31
Entering Operating Parameters to Select Modes
To enter the display:
1. Press the
Mode Display key to view the Run/Stop & Alarm 1 Modes.
2. Press
and to set the higher or lower the values of the
parameter or turn that function On or Off.
The SV readout displays the different values for the parameter within a mode.
3. To switch modes within a level, press and hold the
Level Display
key for one (1) second.
The PV readout will display the different parameters within each mode.
4. Use short presses on the
Mode Display key to display each parameter
within a mode.
The SV readout displays the different values for the parameter within a mode.
5. Press
and to set the higher or lower the values of a parameter
or turn that function On or Off.
6. Press Level Key once to return to the Process Temperature Setting.
Figure 12: Settings for Process Temperature Controller (E5CN), Part No. A0555757
Mode
Parameter Setting range Default
Manuf. setting
Run/Stop Run/Stop Run -
Operation
Alarm value 1 -1999 to 9999 0 25
Mode
Parameter Setting range Default
Manuf. setting
AT execute/cancel ON, OFF OFF ?
Temperature input shift -199.9 to 999.9 0.0 -
Proportional Band 0.1 to 999.9 8.0 ?
Integral Time 0 to 3999 233 ?
Adjustment
Derivative Time 0 to 3999 40 ?