Trane Direct-Fired Indoor and Outdoor Make-Up Air Units Wheelchair User Manual


 
52 Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN
I/O Zone 583 Controller Specifications
LED indication
3 Analog Outputs
–0 - 10 VDC
OUTPUT ASSIGNMENTS - ANALOG
AO1 Burner firing rate (to signal conditioner) 0 - 10 VDC
AO2 RA or Mixing Damper Control/ User Configured 0 - 10VDC
AO3 Unassigned
OUTPUT ASSIGNMENTS - DIGITAL
DO1 Unit Enable
DO2 Burner Enable
DO3 Cooling Enable
DO4 Alarm
DO5 Pilot to Main Flame Sensor Changeover Switch
INPUT ASSIGNMENTS - UNIVERSAL
IN1 Pressure Transducer for Building Pressure Control or User Configured
IN2 Pressure Transducer for Flow Station
IN3 Multiplexed
100% Outside Air/100% Output
Flame Failure Alarm
Safety Circuit Status
Manual/Mixed Air Dmpr Control
IN4 Multiplexed
Auxiliary Unit Enable
Clogged Filter
Fan Status
Burner Status
IN5 Outside Air sensor
IN6 Discharge Air sensor
IN7 Unit Enable/Remote Setpoint
IN8 Damper Control
RNET MRT-Pro or Room Air sensor