MUA-SVP01A-EN • Direct-Fired Indoor and Outdoor Units 3
NETWORKING
AdaptAire is adaptable to a variety of different network architectures and
protocols. Each controller has built-in protocol translation and can be configured
for operation on ARCnet156 or EIA-485 communication networks. See Appendix
IV for specific controller specifications.
The AdaptAire system can be connected to most existing building automation
systems. Some systems may require the use of special controllers and network
communication devices. See Appendix I for Device Parameters and Cache Setup
information.
ADAPTAIRE DEFAULT SETTINGS
The following is a list of AdaptAire DDC controller defaults. These are the default
operating parameters set at the factory prior to shipment.
Table 1. Default settings
ITEM DEFAULT RANGE
Unit Network Address 002 binary dips 000 – 255 binary dips
Unit Operating Mode OFF OFF – MANUAL - AUTO
Time Clock Schedule None 4 Daily - 12 Holiday - 2
Override schedules
Heating/Cooling Operating
Mode
Heating HEATING - COOLING
Damper Operating Mode Manual MANUAL - BUILDING
PRESS - MIXED AIR
TEMP
Fuel Selection Natural Gas NATURAL - PROPANE
Heating Night Setback 55°F 40°F - 80°F
Cooling Night Setback 100°F 75°F - 120°F
Room Temperature Setpoint 65°F 55°F - 90°F
Freezestat 45°F 35°F - 50°F
Outside Air Economizer
Setpoint
65°F 40°F - 80°F
Minimum Discharge
Temperature Setpoint
55°F 40°F - 130°F
Maximum Discharge
Temperature Setpoint
100°F 55°F - 130°F
Mixed Air Temperature
Setpoint
50°F 30°F - 90°F
Building Pressure Setpoint 0” W. C. -0.05” - +0.05” W. C.
Manual Damper Position
Setpoint
20% Outside Air 0% - 100%
Minimum Ventilation
Setpoint
20% Outside Air 0% - 100%
User PID Select Direct Acting DIRECT -REVERSE
High Input Value 0 -9999.99 – 99999.99