Trane Direct-Fired Indoor and Outdoor Make-Up Air Units Wheelchair User Manual


 
44 Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN
Menu Selection
Status
Alarm
SET POINTS HOTKEY - 3
Htg Occupied °F range 55-90
Htg Setback °F range 40-80
Htg Min DA °F range 40-130
Htg Max DA °F range 55-130
Clg Occupied °F range 61-96
Clg Setback °F range 75-130
Clg Min DA °F range 40-130
Clg Max DA °F range 55-130
Man Vent %OA range 0-100
Mixed Air °F range 30-80
Bldg Prs "WC range -0.05-+0.05
Min Vent % range 0-100
Economizer Temp °F range 40-80
Freeze Stat °F range 35-80
Home
Status
Alarm
Resets