MUA-SVP01A-EN • Direct-Fired Indoor and Outdoor Units 51
POWER REQUIREMENTS. 24VAC ± 10%, 20VA
NETWORK COMMUNICATION
BACnet (native), Modbus RTU, or N2 bus at up to 76.8K baud or 156K baud over
ARCnet. LonWorks using plug-in communications board.
USER INTERFACE
MDT: modulating discharge temperature control with manually adjusted
potentiometer at remote panel.
MRT: modulating room temperature control with manually adjusted
potentiometer at remote panel.
MRT-Pro: modulating room temperature control with intelligent room
thermostat.
MRT-Expert: modulating room temperature control with intelligent room sensor
and BACview LCD control panel.
MEMORY
1M bytes of flash memory and 512K
bytes of non-volatile battery-backed
RAM
REALTIME CLOCK
Battery-backed to keep time in event of power failure.
TEMPERATURE OPERATING RANGE
0°F to 130°F, 10% to 95% RH non-condensing
INPUTS/OUTPUTS
8 Universal Inputs
Inputs 1 & 2
Dry, thermistor, 0-5VDC
Inputs 3 - 6
–oDry, thermistor
Inputs 7 & 8
1k -10k pot
5 Digital Outputs
Relay contacts rated at 1A Resistive @ 24VAC
I/O Zone 583 Controller Specifications