Honeywell Y8610U Oxygen Equipment User Manual


 
Y8610U INTERMITTENT PILOT RETROFIT KIT
13 68-0291—03
Connect Ignition Cable
Use the provided ignition cable to connect the S8610U module
to the pilot burner.
Be sure the ignition cable is not exposed to high temperature
while the appliance is operating.
NOTE: The cable must not run in continuous contact with a
metal surface or spark voltage may be greatly
reduced. Use ceramic or plastic standoff insulators as
required.
To install:
1. Connect one end of the cable to the male quick connect
SPARK terminal on the ignition module.
2. Connect the other end of the cable to the igniter or
igniter-sensor stud on the pilot burner/igniter-sensor.
Wiring Connections
Connect the provided harness to the ignition module and the
gas control. The harness ends are labeled for easy installation.
See Table 4.
Use Fig. 15 and Table 5 to make the remaining wiring
connections.
NOTE: The 24V terminal on the S8610U is used only when a
vent damper is installed.
Fig. 16 on page 14 illustrates the typical wiring connections in
a heating system with an atmospheric burner.
Fig. 15. S8610U Typical wiring connections.
Table 4. Wiring Harness Connections.
Harness Wire Color
/ Wire Label
S8610U
Terminal
Gas Control Terminal
/ Tstat Load
Black / 25 VAC TH-W Thermostat call for
heat to original
standing pilot valve
Orange / 25 VAC-GND 24V (GND) Transformer 24 VAC
ground lead to original
standing pilot valve
Red / MV MV MV
White / MV-PV MV-PV MV-PV
Blue / PV PV PV
Green / GND GND Ground terminal on
gas control
Table 5. S8610U Typical Wiring Connections.
Connector
Label
Size or
Type Description
MV 1/4 inch Main Valve connection
MV/PV 1/4 inch Common terminal for gas valves
PV 1/4 inch Pilot Valve connection
BRN GND 1/4 inch Burner Ground
24V GND 1/4 inch Return path to transformer
24V 1/4 inch Optional—
24 Vac power connection for Vent
Damper
TH-W 1/4 inch Connector for “Call for Heat” signal
from thermostat
P1 6-pin
keyed plug
Connector for Vent Damper
connection (used to control a
connected damper in atmospheric
appliances)
Flame
Current
Two holes Micro-ammeter connector
P4
(Jumper)
Jumper Provides a lockout for the DIP
switch settings (See “Jumper” on
page 15.)
SENSE
JUMPER
WIRE
Wire with
3/16 inch
quick
connect
Connects to the REMOTE SENSE
connector for installations with a
single spark rod (local flame
sensing)
REMOTE
SENSE
3/16 inch Flame Sensor connector
For single rod installations, connect
the SENSE JUMPER WIRE to this
terminal connector.
SPARK 1/4 inch High voltage sparking electrode
connection
SPARK
MV
24V GND
MV/PV
PV
BRN/GND
REMOTE
SENSE
TH-W (OPT.)
24V (OPT.)
M29890
SENSE
JUMPER
WIRE
P1 VENT DAMPER
CONNECTOR