3. Remove outer and inner control panel covers. Install the 3 pin accessory plug from
the parts bag into the control panel if not already equipped. See figure 6A for side
installation the 5 or 6 ton cabinet size. See figure 6B for back installation on the 2
and 3 ton cabinet size.
4. Plug the WUVCLP light into the 3 pin accessory plug just installed. Plug located on
the side or back of the control panel. Secure mounting bracket to control panel with
screws provided.
5. Route the flexible conduit from the light across the blower partition and into the
transformer box. Secure the conduit to the box with the fitting supplied. (See Figure
9)
6. Remove the nut securing the transformer foot to the box and connect the ground
wire to this bolt. Reinstall the nut. Connect the black wire from the UV light to one of
the black transformer secondary wires with the wire nut provided. Connect the red
wire from the UV light to the other transformer secondary wire with the wire nut
provided.
7. Place the transformer protective shield over top of the transformer and wires and
fasten into place. (See Figure 8)
8. Remove 2 screws holding the back of the blower partition to the drain pan. Install
two metal conduit clips supplied to hold the flexible conduit in place along the back
of the control panel. Reinstall the screws. (See Figure 9) Caution: Do not leave
wires exposed to the UV light or the insulation will decay thus causing an electrical
hazard.