BAC-10000 Series 8 Operation Guide, Rev. J
(Advanced) Temp. Setpoint Limits
LIMITS
OCC MIN CLG:
OCC MAX HTG: 76° F
UNOCC MIN CLG: 77° F
UNOCC MAX HTG: 65° F
71° F
To set the minimum and maximum allowed user/
operator setpoint values, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
(Advanced) Motion Sensor
MOTION SENSOR
MOTION OCC:
STATE: OCCUPIED
ENABLE
In BAC-11xxx models, a motion/occupancy sensor
may be enabled to trigger occupancy override.
During scheduled “o” times, the motion sensor will
start occupancy override (for 1 hour as a default)
when it detects motion. Occupancy override will end
(with the default seing) 1 hour aer motion was
last detected. The length of occupancy override is
congurable in the System menu. See System Setup
on page 13.
To enable/disable or monitor the motion/occupancy
sensor (if installed), press:
1. Enter to select.
2. Right/Le to move among value elds.
3. Up/Down to increment/decrement value.
The State eld monitors whether motion has been
detected during the last scan of the motion sensor
input (BI6). Detected motion will show an “occu-
pied” state. This can be used during troubleshooting
to determine if motion is being detected.
(Advanced) BACnet Device Properties
DEVICE
INSTANCE:
NAME: FlexStat_101
LOCATION: KMC Controls
RESTART: NO
RESTORE FACTORY: NO
1
To set the BACnet device instance, name, and
location, press:
1. Up/Down to move among entries.
2. Enter to select.
The FlexStat can also be restarted or restored to
factory defaults from this menu. See Reseing the
FlexStat on page 14 for more information about that
function.
(Advanced) Inputs
INPUTS
1: SPACE TEMP
2:
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
4: SPACE HUMIDITY
DISCH AIR TEMP
INPUT #2
DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
SENSOR:
10K TYPE III
Inputs vary according to model, selected application,
and selected application options. See (Advanced) Ap-
plication Options on page 5.
To change sensor type and calibration oset, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
Value will show a temperature reading or a voltage
(0.0 to 3.0), depending on the sensor. Analog sensors
can be calibrated using the Calibration Oset option.