BAC-10000 Series 15 Operation Guide, Rev. J
Restore Factory
Restore Factory (restoring the FlexStat to the factory
seings) does the following:
• Clears present values.
• Restores the object database/conguration to the
defaults.
• Restarts the controller’s (factory installed) Con-
trol Basic programs.
NOTE: The MAC address and device instance are
not restored to their original defaults, and
custom Control Basic programs are not
deleted. If custom Control Basic programs are
installed, all factory programs are restarted
but all custom Control Basic programs are
halted. Custom programs may be restarted by
loading/running the programs from the CB
Programs menu. See (Advanced) CB (Control
Basic) Programs on page 6.
CAUTION
When returned to factory defaults, analog out-
puts will go to zero and relays will go to their
normally open state. Before restarting the ther-
mostat, manually override equipment as needed.
ADVANCED
APPLICATION
CB PROGRAMS
COMMUNICATION
DATE/TIME
DEVICE
LIMITS
SECURITY
DEVICE
INSTANCE: 1
NAME: FlexStat_101
LOCATION: KMC Controls
RESTART: NO
RESTORE FACTORY:
YES
RESTART REQUIRED!
CANCELRESTART
CAUTION
After a return to factory defaults, applications are
unconfigured. You must select the desired appli-
cation and appropriate settings before connected
equipment will operate properly. (See (Advanced)
Application Options on page 5.)
To restore the FlexStat to factory seings:
1. Select Restore Factory from the Advanced > De-
vice menu.
2. When prompted for the required restart, press
Enter. (To Cancel, press the right buon and then
Enter or just let the display time-out).
3. Aer the FlexStat has restarted, review the set-
tings and recongure as needed.