BAC-10000 Series 4 Operation Guide, Rev. J
Configuration (Initial Setup)
NOTE: Menus shown in this document reect
rmware version R1.3.0.4 or later. Actual
context-sensitive screens are dependent
on rmware version, FlexStat model, and
options selected.
NOTE: If appear at the top of the screen
(such as in the Main Menu), scroll up or
down to see the rest of the menu’s o-
screen choices.
Main Menu Overview
MAIN MENU
ABOUT
ADVANCED
ALARM
DATE/TIME
SCHEDULE
SETPOINTS
SYSTEM
Navigate the menus and change seings by pressing
a combination of buons. Press the:
• Enter buon to select and/or exit value editing.
• Up/Down buon to move among entries (up/
down lines).
• Le/Right buon to move among value elds
(le/right spaces).
• Le buon to return to the Home screen.
NOTE: A log-in may be required to access menu
items.
SETPOINTS
COOL SETPT:
HEAT SETPT: 67° F
COOL SETBACK: 80° F
SAVE CHANGE?
NO
YES
When prompted about a change (on any menu),
press Right/Le to select the desired choice and
then Enter.
About the FlexStat
ABOUT FLEXSTAT
FW: R1.3.0.0
BUILT: DEC 11 2009 @13:55:07
ASV: BAC_1xx63 R1.3.0.0 +6
MODEL: BAC–11163C
APP: AIR HANDLER
OPT: MOD H / MOD C
INSTANCE: 1
This display-only screen shows (scroll to see all):
Firmware version (FW)
Build date
Application soware version (ASV)
Model number
Application conguration and options (set in the
Application menu)
Device instance (set in the Device menu)
MAC address (set in the Communications menu)
Serial number
Board revision
NOTE: ASV will show CUSTOM if any built-in
Control Basic program (1–5) is not running
or has auto-run disabled.