Emerson 3051S Pacemaker User Manual


 
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
17
SAFETY INSTRUMENTED SYSTEMS
Additional Safety Instrumented Systems information is available in the
Rosemount 3051S reference manual (document number
00809-0100-4801). The manual is available electronically on
www.rosemount.com or by contacting an Emerson Process
Management representative.
3051S Safety-Certified Identification
All 3051S transmitters must be identified as safety-certified before
installing into SIS systems.
NOTE
There are two versions of safety-certified 3051S pressure transmitters.
For transmitters with a yellow SIS circuit board installed and output
code B in the model number, please refer to Manual Supplement
00809-0700-4801.
To identify a safety-certified 3051S:
1. Connect a HART host to the transmitter.
2. Check the software to verify that the software revision is 7 or
higher.
Fast Key Sequence - 1, 5
3. Verify that option code QT is included in the transmitter model
code.
Revision #’s
Fld Dev Rev 7
Software Rev 7
Hardware Rev 16
4801_QIG_RevHA.fm Page 17 Tuesday, February 26, 2008 12:17 PM