Emerson 3051S Pacemaker User Manual


 
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
11
STEP 4 CONTINUED...
2. Place coupling nut over quick connect and wrench tighten to a
maximum of 300 in-lb. (34 N-m).
3. Tighten the set screw using a
3
/32-in hex wrench.
4. Install Cordset/ Field Wireable Connectors onto the Quick Connect.
Do not over tighten.
Figure 6. Quick Connect Housing Pin-Out
Conduit Electrical Connector Wiring (Option GE or GM)
For 3051S transmitters with conduit electrical connectors GE or GM,
refer to the cordset manufacturer’s installation instructions for wiring
details. For FM Intrinsically Safe, non-incendive or FM FISCO
Intrinsically Safe hazardous locations, install in accordance with
Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X
and IP66.) See Appendix B of the 3051S reference manual.
For other wiring
details, refer to pin-out
drawing and the
cordset
manufacturer’s
installation
instructions.
“+”
“–”
Ground
No Connection
4801_QIG_RevHA.fm Page 11 Tuesday, February 26, 2008 12:17 PM