STEP 5 CONTINUED...
Set the Display Equivalent to a 4 mA Signal
1. Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover.
2. Press the left button for two seconds.
3. To decrement the display numbers, press the left configuration button and to increment
the numbers, press the right configuration button. Set the numbers between –999 and
1000.
4. To store the information, press both configuration buttons simultaneously for two
seconds.
5. Replace the LCD display cover.
Set the Display Equivalent to a 20 mA Signal
1. Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover.
2. Press the right button for two seconds.
3. To decrement the display numbers, press the left configuration button on the display and
to increment the numbers, press the right configuration button. Set the numbers between
–999 and 9999. The sum of the 4 mA point and the span must not exceed 9999.
4. To store the information, press both configuration buttons simultaneously for two
seconds. The LCD display is now configured.
5. Replace the LCD Display cover.