Engineering Guideline EH-150 Series PLC
Fieldbus Master Modules
1
EH-RMP
EH-RMD
Profibus-DP
DeviceNet
Type
Class 1 Profibus-DP master
DeviceNet
TM
2.0
Supported by CPU's
EH-CPU308, EH-CPU316, EH-CPU448
EH-CPU308, EH-CPU316, EH-CPU448
Max. number of modules
2/CPU (Slot 0-2)
2/CPU (Slot 0-2)
Max. number of Slaves
124
63
Output data
256 words
256 words
Input data
256 words
256 words
9.6 kbps
1200m
-
19.2 kbps
1200m
-
45.45 kbps
1200m
-
93.75 kbps
1200m
-
125 kbps
-
500m
187.5 kbps
1000m
-
250 kbps
-
250m
500 kbps
400m
100m
1500 kbps
200m
-
3 Mbps
100m
-
6 Mbps
100m
-
12 Mbps
100m
-
Approx. 600mA
Approx. 600mA
LINK
LINK
9 pin D-sub, female
5-pole DeviceNet connector
Double shielded twisted pair cables
according to Profibus specification
DeviceNet
TM
dedicated cable
System ROM/RAM check, watch-dog
timer check
System ROM/RAM check, watch-dog
timer check
Link area 1
Output area starts at WL0, Input area
starts independent from Link area setting
allways at WL200
Output area starts at WL0, Input area
starts independent from Link area setting
allways at WL200
Link area 2
Output area starts at WL1000, Input area
starts independent from Link area setting
allways at WL1200
Output area starts at WL1000, Input area
starts independent from Link area setting
always at WL1200
-
EDS-file, File name:Eh_rmd_1_1.eds.
This file can either be downloaded from
the web (www.hitachi-ds.com) or received
by contacting Hitachi Europe
Profibus configurator software,
Order-Number: PBDP-M-CONF
DeviceNet configurator RSNetworx and
dedicated interface adapter
Item
Fieldbus system
External wiring
General
Function
Internal current consumption (5V)
I/O assignment
External connection
Max. segment
length (at data
transfer rate).
Configurator software
Self diagnosis
Link area settings
File for configuration