Engineering Guideline EH-150 Series PLC
4
*1: The module needs to be repaired in case the fuse is blown. The fuse cannot be replaced by the customer.
Maximum load current
Output response time
Minimum switching current
Electronic short circuit protection
External power supply
Internal current consumption (5V)
Transistor output (source type)
Removable type screw terminal block
12/24V DC (+10%, -15%, maximum 30mA)
Transistor Output Modules, Source Type
EH-YR12 EH-YS4
Relay output Triac output
Y16 Y16
100/240V AC, 24V DC 100/240V AC (85 to 250V AC)
1mA 100mA
none 5mA or less
Output 2A 0.5A
Common 5A 2A
OFF -> ON 10ms or less 1ms or less
ON -> OFF 10ms or less 1ms + 1/2 cycle or less
12 4
1 1
None Varistor
None 4A
Photocoupler Photo triac
Approx. 40mA Approx. 100mA
24V DC (+10%, -5%, maximum
70mA)
100/240V AC (85 to 250V AC)
Item
Output specification
Minimum switching current
Leak current
I/O assignment
Rated load voltage
Number of output points
Number of common points
Surge removal ladder
Maximum load current
Output response time
Removable type screw terminal block
LED's (green)
Fuse
Insulation system
Internal current consumption (5V)
External power supply
(Module supply voltage)
Output display
External connection
Digital Output Modules