A SERVICE OF

logo

FS-8700-88 Envirotronics SystemsPlus Page 33 of 49
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.4.82. Map Descriptor Example 79 - set time = hour:minute:second
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function,
Node_Name, SysPlus_Cmd, Par_Data_Array_Name, Par_Data_Array_Offset, Length
Set_Time, Par_Bit_Triggers, 4, awt, SYSPLUS_01, Set_Time, Set_Time, 0, 1
This command is used by first writing the parameter data and then triggering the command by writing any value to Data_Array_Name
at Data_Array_Offset.
Parameter data setup:
Offset from par_data_array_offset Description
0
Hour
1
Minute
2
Second
4.4.83. Map Descriptor Example 80 - edit set setpoint channel = value
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function,
Node_Name, SysPlus_Cmd, Par_Data_Array_Name, Par_Data_Array_Offset, Length
Ed_Set_Setpoint, Par_Val_Trigger, 0, awt, SYSPLUS_01, Ed_Set_Setpoint, Ed_Set_Setpoint, 0, 1
This command is used by first writing the parameter data value and then triggering the command by writing channel to
Data_Array_Name at Data_Array_Offset.
Parameter data setup:
Offset from par_data_array_offset Description
0
Value