FS-8700-88 Envirotronics SystemsPlus Page 18 of 49
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.4.29. Map Descriptor Example 26 - set audible alarm = Boolean
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Data_Type, Length
Audible_Alarm, Audible_Alarm_0, 0, wrbx, SYSPLUS_01, Audible_Alarm, 1
A Boolean value of 1 for “on” or 0 for “off” must be written to Data_Array_Name at Data_Array_Offset to trigger this command.
4.4.30. Map descriptor Example 27 - read software version
// Cleint Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Data_Type, Length
Sw_Version, 0s, Sw_Version, 0, rdbc, SYSPLUS_01, Sw_Version, 1
4.4.31. Map Descriptor Example 28 - read events
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Data_Type, Length
All_Event_States, 0s, All_Event_States, 0, rdbc, SYSPLUS_01, All_Events, 10
The retrieved event states will be stored as follows in Data_Array_Name:
( A value of 1 will be stored for “on” or 0 for “off” )
Offset from Data_Array_Offset Description
0 Event_0 state
1 Event_1 state
2 Event_2 state
.. ..
9 Event_9 state