4.4.32. Map Descriptor Example 29 - read auxs
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Data_Type, Length
All_Aux_States, 0s, All_Aux_States, 0, rdbc, SYSPLUS_01, All_Auxs, 10
The retrieved aux states will be stored as follows in Data_Array_Name: (A value of 1 will be stored for “on” or 0 for “off”)
Offset from Data_Array_Offset Description
0 Aux_0 state
1 Aux_1 state
2 Aux_2 state
.. ..
9 Aux_9 state
4.4.33. Map Descriptor Example 30 - read alarm status alarm
// Client Side Map Descriptors
Map Descriptor
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function,
Node_Name, SysPlus_Data_Type, SysPlus_Alarm_Name, Length
Alarm_Sts_00, 0s, Alarm_Statuses, 0, rdbc, SYSPLUS_01, Alarm, volt, 1
alarm is specified by the name under SysPlus_Alarm_Name. The status of the alarm will be stored as 1 for “OK” or 0 for “FAIL” in
Data_Array_Name at Data_Array_Offset.
4.4.34. Map Descriptor Example 31 - emergency stop
// Client Side Map Descriptors
Map Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Cmd, Length
Emergency_Stop, ProgSysControl, 0, wrbx, SYSPLUS_01, Emergency_Stop, 1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.