Page 12
PROGRAM INSTRUCTIONS (cont)
7. Depress MODE (S1) switch once.
The text followed by the current value of Hysteresis Low will
be displayed. Repeat Step 2 to set Alarm Hysteresis Low to the
desired value. The maximum value for HL is 99 counts. Proceed to
Step 8 or depress S4 to exit.
8. Depress MODE (S1) switch once.
The text followed by the current CAL number will be
displayed. Use S2 & S3 to set the Cal Number. Remember the Cal
Value should be between 2000 & 19000 (decimal not used).
Proceed to Step 9 or depress S4 to exit.
9. Depress MODE (S1) switch once.
The text followed by the current decimal position will be
shown flashing. Use S2 to set the decimal point to the desired
location.
10. Depress MODE (S1) switch once.
The instrument will exit the Mode Selection Sequence and enter
the normal operating mode (i.e. monitoring the input signal) This
is the end of the PROGRAM INSTRUCTIONS.