18
1006H Heating/Cooling control selection Refer to Ouputput Mode Selection
1007H 1st group of Heating/Cooling
control cycle
1~990, unit is 0.1 second. When the output setting = realy, the minimum control
cycle is 5 second
1008H 2nd group of Heating/Cooling
control cycle
1~990, unit is 0.1 second. When the output setting = realy, the minimum control
cycle is 5 second 1~990
1009H PB Proportional band 0.1 ~ 999.9
100AH Ti Integral time 0~9,999
100BH Td Derivative time 0~9,999
100CH Integration default 0 ~ 100%, unit is 0.1%
100DH Proportional control offset error
value, when Ti=0
0 ~ 100%, unit is 0.1%
100EH The setting of COEF when Dual
Loop output control are used
0.01 ~99.99, unit is 0.01
100FH The setting of Dead Band when
Dual Loop output control are
used
-999 ~ 9,999
1010H Hysteresis setting value of the
1st output group
0~9,999
1011H Hysteresis setting value of the
2nd output group
0~9,999
1012H Output value read and write of
Output 1
Unit is 0.1%, write operation is valid under manual tuning mode only.
1013H Output value read and write of
Output 2
Unit is 0.1%, write operation is valid under manual tuning mode only.
1016H Temperature regulation value -99.9 ~ +99.9. Unit is 0.1
1017H Analog decimal setting 0 ~ 3
101CH PID parameter selection 0~5/AUTO
101DH SV value corresponded to PID
value
Only valid within available range, unit: 0.1 scale
1020H Alarm 1 type Please refer to the contents of the “Alarm Outputs” for detail
1021H Alarm 2 type Please refer to the contents of the “Alarm Outputs” for detail
1022H Alarm 3 type Please refer to the contents of the “Alarm Outputs” for detail
1024H Upper-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail
1025H Lower-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail
1026H Upper-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail
1027H Lower-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail
1028H Upper-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail
1029H Lower-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail
102AH Read LED Status b0: ALM3, b1: ALM2, b2: , b3: , b4: ALM1, b5: OUT2, b6:OUT1, b7: AT℉℃
102BH Read Pushbutton Status b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key
102CH Setting lock status
102FH Software version V1.00 indicates 0x100
1030H Start pattern number 0 ~ 15
1200H~13FFH
Pattern 0~15 temperature set
point setting (Even number)
Pattern 0~15 execution time
setting (Odd number)
-999 ~ 9999
Time: 0 ~ 900(1 minute per scale)
1400H~140FH
Actual number of step setting
inside the corresponding pattern
0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N
1410H~141FH
Cycle number for repeating the
execution of the correspond
pattern
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
1420H~142FH
Link pattern number setting of
the correspond pattern
0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the
program end and execution end. 0~15 indicates the next execution pattern
number after executing the current pattern
Address Content Definition
1100H Adjust Temperature Gain
1101H Temperature Filter Range Range of temperature filter: 10~1000, unit: 0.01 ℃, default: 100(1.0℃)
1102H Temperature Filter Factor Setting range: 0~50, default: 8