50
RT-PRC002-EN
*Indicates both downflow and horizontal units.
Electrical
Data
Table ED-1 — Unit Wiring — Standard Efficiency
Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity
2
Circuit Breaker
1
Ampacity
2
Circuit Breaker
1
TC*150D3 187-253 63 80 69 80
12½ TC*150D4 414-506 33 40 36 40
TC*150DW 518-633 26 30 28 35
TC*150DK 342-418 43 50
TC*180B3 187-253 78 90 84 100
15 TC*180B4 414-506 39 50 42 50
TC*180BW 517-633 31 40 33 40
TC*180BK 342-418 50 60
TC*210C3 187-253 88 100 96 125
17½ TC*210C4 414-506 44 50 47 60
TC*210CW 517-633 35 45 38 45
TC*210CK 342-418 57 70
TC*240B3 187-253 100 125 107 125
20 TC*240B4 414-506 50 60 54 60
TC*240BW 517-633 40 45 43 50
TC*240BK 342-418 65 80
TC*300B3 187-253 118 150
25 TC*300B4 414-506 58 70
TC*300BW 517-633 46 50
TC*300BK 342-418 70 80
Notes:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.
(Standard Efficiency)