![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/5/d5/5d5a9342-4ac8-451b-8833-e34262c1ada3/5d5a9342-4ac8-451b-8833-e34262c1ada3-bg11.png)
17
RT-PRC002-EN
Performance
Data
(12½, 15 Ton)
Standard Efficiency
*Indicates both downflow and horizontal units.
Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*150D3, D4, DW, DK
Ambient Temperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5
4500 80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6
85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5
90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0
75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6
5000 80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2
85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9
90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0
75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9
5500 80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7
85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0
90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0
75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0
6000 80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5
85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8
90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*180B3, B4, BW, BK
Ambient Temperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2
5400 80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7
85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0
90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0
75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9
6000 80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0
90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0
75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1
6600 80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6
85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0
75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2
7200 80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4
85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0
90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to
appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity