Fluid leakage Loose joints Tighten joints.
Dirty gasket Clean gasket and seat area.
Bad gasket Replace gasket.
Counter reading Calibration off Recalibrate meter.
high or low Air in product Find and repair air leaks in system.
Measuring chamber or gears sticking Clean or replace internal metering components.
Meter shaft seal Dirty seal Clean O-ring seal and seat area.
leakage Bad seal Replace seal.
TROUBLESHOOTING GUIDE
PROBLEM POSSIBLE CAUSE SOLUTION
9
ABOVEGROUND TANK INSTALLATION
NOTE:
USE APPROVED PIPE COMPOUND
ON ALL PIPE THREADS.
ELECTRICAL NOTE:
ELECTRICAL WIRING SHOULD BE DONE IN ACCORDANCE WITH APPROVED LOCAL
ELECTRICAL CODES AND BY A LICENSED ELECTRICIAN. THE PUMP SHOULD BE
PROPERLY GROUNDED, AND RIGID CONDUIT SHOULD BE USED WHEN INSTALLING
ELECTRICAL WIRING. WARNING: FAILURE TO FOLLOW THESE WIRING INSTRUCTIONS
MAY RESULT IN SERIOUS INJURY FROM ELECTRICAL SHOCK.