Dimensions
30XW UNIT DIMENSIONS
30XW UNIT AND WATERBOX DIMENSIONS
NOTES:
1. Operating weight includes weight of water, refrigerent, and oil.
2. Denotes center of gravity.
3. Dimensions shown in ft-in. [mm] unless noted.
4. The recommended service clearance around the machine is 3 ft [914.4 mm].
5. Victaulic nozzles are standard on all units. A flow switch can be factory-installed in evaporator inlet victaulic nozzle.
6. Maximum fluid side pressure of condenser or evaporator is 150 psig [1034 kPa] (standard) or 300 psig [2068 kPa] (optional).
7. Operating weight includes weight of water, refrigerant, and oil.
CONNECTIONS PASSES
WATERBOX
(EVAP/COND)
NOZZLE
TYPE
D
ft-in. [mm]
E
ft-in. [mm]
F
ft-in. [mm]
MAX UNIT OPERATING WEIGHT lb [kg]
325 350 400
Same Ends
2 Pass
NIH/NIH
Victaulic 13-3
3
/
4
[4057]
3-11
3
/
8
[1210] 6-6
11
/
16
[1999]
14,319 [6495] 14,515 [6495] 14,759 [6695]
Flange 13-9
1
/
16
[4193] 14,651 [6646] 14,847 [6646] 15,091 [6845]
NIH/MWB
Victaulic
13-11
5
/
8
[4258]
14,498 [6576] 14,694 [6576] 14,938 [6776]
Flange 14,739 [6685] 14,935 [6685] 15,179 [6885]
MWB/NIH
Victaulic 14,489 [6572] 14,685 [6572] 14,929 [6772]
Flange 14,746 [6689] 14,768 [6689] 15,012 [6809]
MWB/MWB
Victaulic 14,668 [6653] 14,864 [6653] 15,108 [6853]
Flange 14,834 [6729] 15,030 [6729] 15,274 [6928]
Opposite Ends
NIH/NIH
Victaulic 13-6
5
/
16
[4123]
3-11
3
/
8
[1210] 6-6
11
/
16
[1999]
14,319 [6495] 14,515 [6495] 14,759 [6695]
Flange 14-4
7
/
16
[4380] 14,651 [6646] 14,847 [6646] 15,091 [6845]
NIH/MWB
Victaulic 14-2
3
/
16
[4323] 14,498 [6576] 14,694 [6576] 14,938 [6776]
Flange 14-6
15
/
16
[4443] 14,739 [6685] 14,935 [6685] 15,179 [6885]
MWB/NIH
Victaulic 14-2
13
/
16
[4339] 14,489 [6572] 14,685 [6572] 14,929 [6772]
Flange 14-8
3
/
16
[4475] 14,746 [6689] 14,768 [6689] 15,012 [6809]
MWB/MWB
Victaulic
14-10
11
/
16
[4539]
14,668 [6653] 14,864 [6653] 15,108 [6853]
Flange 14,834 [6729] 15,030 [6729] 15,274 [6928]
1 or
3 Pass
NIH/NIH Flange 14-5
5
/
8
[4410] 14,828 [6726] 15,024 [6726] 15,268 [6925]
NIH/MWB Flange
14-10
11
/
16
[4539]
15,223 [6905] 14,768 [6896] 15,012 [6809]
MWB/NIH Flange 15,244 [6915] 15,440 [6894] 15,684 [7114]
MWB/MWB Flange 15,581 [7067] 15,777 [7063] 16,021 [7267]
SUCTION
END
DISCHARGE
END
EVAPORATOR
CONDENSER
SEE NIH CONDENSER
DETAIL FOR NOZZLE
MEASUREMENTS
SEE NIH EVAPORATOR
DETAIL FOR NOZZLE
MEASUREMENTS
MLV (OPTIONAL)
MLV (OPTIONAL)
a30-4745
STANDARD 30XW UNIT DIMENSIONS
NOTES:
1. Weights shown for standard chiller (2 pass with NIH, victaulic waterboxes).
2. See page 14 for unit mounting locations.
30XW UNIT
SIZE
OPERATING
WEIGHT, lb [kg]
MOUNTING LOCATION WEIGHT, lb [kg] DIMENSIONS (ft-in. [mm])
1234ABC
325 14,319 [6495] 3734 [1694] 3828 [1736] 3337 [1514] 3420 [1551] 6-
3
/
8
[1837] 6-
3
/
8
[1837]
3
/
8
[9.53]
350 14,515 [6584] 3785 [1717] 3880 [1760] 3383 [1535] 3467 [1573] 6-
3
/
8
[1837] 6-
3
/
8
[1837]
3
/
8
[9.53]
400 14,759 [6695] 3848 [1745] 3946 [1790] 3439 [1560] 3526 [1599] 6-
3
/
8
[1837] 6-
3
/
8
[1837]
3
/
8
[9.53]
LEGEND
MLV Minimum Load Valve
MWB Marine Waterbox
NIH Nozzle-In-Head
SSV Suction Service Valve