START-UP CHECKLIST
MODEL NO.:
DATE:
SERIAL NO.:
TECHNICIAN:
I. PRE-START-UP:
Ⅺ VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
Ⅺ VERIFY INSTALLATION OF INDOOR FAN MOTOR ADJUSTMENT BOLT (180 UNITS) OR ADJUSTMENT
BOLT AND PLATE (216-300 UNITS)
Ⅺ OPEN ALL SERVICE VALVES (SUCTION, DISCHARGE, AND LIQUID)
Ⅺ VERIFY INSTALLATION OF ECONOMIZER HOOD
Ⅺ VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
Ⅺ VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
Ⅺ CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE
Ⅺ VERIFY THAT UNIT IS LEVEL
Ⅺ CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW
IS TIGHT
Ⅺ VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
Ⅺ VERIFY THAT SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
II. START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1
COMPRESSOR AMPS — COMPRESSOR NO. 1 L1 L2 L3
— COMPRESSOR NO. 2 L1 L2 L3
SUPPLY FAN AMPS EXHAUST FAN AMPS
ELECTRIC HEAT AMPS (IF SO EQUIPPED) L1 L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE F DB (Dry-Bulb)
RETURN-AIR TEMPERATURE
FDB F WB (Wet-Bulb)
COOLING SUPPLY AIR
F
ELECTRIC HEAT SUPPLY AIR (IF SO EQUIPPED)
F
PRESSURES
REFRIGERANT SUCTION CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 (216-300 ONLY) PSIG
REFRIGERANT DISCHARGE CIRCUIT NO. 1
PSIG CIRCUIT NO. 2 (216-300 ONLY) PSIG
Ⅺ VERIFY REFRIGERANT CHARGE USING CHARGING CHART ON PAGE 24
GENERAL
Ⅺ ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS
Ⅺ VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 1998 Bryant Heating & Cooling Systems CATALOG NO. 5355-900