A SERVICE OF

logo

Table 5 Fan Performance 559F180
559F180 (15 TONS)
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
4500 684 1.28 1102 791 1.49 1283 887 1.70 1466 977 1.92 1652 1061 2.13 1841 1139 2.36 2034
4800 715 1.47 1265 817 1.68 1451 910 1.90 1638 997 2.12 1828 1078 2.34 2021 1155 2.57 2217
5100 747 1.67 1442 844 1.89 1633 934 2.12 1825 1018 2.34 2019 1097 2.57 2216 1171 2.80 2416
5400 779 1.90 1635 872 2.12 1831 959 2.35 2027 1040 2.58 2226 1117 2.81 2426 1189 3.05 2629
5700 812 2.14 1844 901 2.37 2044 985 2.60 2245 1063 2.84 2448 1138 3.07 2652 1209 3.31 2858
6000 845 2.40 2068 931 2.64 2273 1011 2.87 2478 1087 3.11 2685 1160 3.35 2893 1229 3.60 3103
6300 878 2.68 2309 961 2.92 2518 1039 3.16 2728 1112 3.41 2939 1183 3.65 3151 1250 3.90 3365
6600 912 2.98 2566 992 3.22 2780 1067 3.47 2994 1138 3.72 3209 1207 3.97 3425 1273 4.22 3642
6900 946 3.29 2841 1023 3.55 3059 1096 3.80 3277 1165 4.05 3496 1232 4.31 3716
7200 981 3.63 3133 1055 3.89 3355 1125 4.15 3578
7500 1016 3.99 3443 1087 4.25 3669
559F180 (15 TONS) (cont)
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.4 1.6 1.8 1.9 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
4500 1214 2.59 2230 1285 2.82 2430 1353 3.05 2633 1386 3.17 2736 1418 3.29 2839
4800 1228 2.80 2417 1297 3.04 2619 1364 3.27 2825 1396 3.40 2928 1428 3.52 3033
5100 1243 3.04 2618 1311 3.27 2823 1376 3.51 3031 1408 3.64 3136 1439 3.76 3242
5400 1259 3.29 2835 1326 3.53 3043 1390 3.77 3254 1421 3.90 3360 1452 4.02 3467
5700 1277 3.56 3067 1342 3.80 3278 1405 4.05 3492 1435 4.17 3600 1466 4.30 3708
6000 1295 3.84 3316 1359 4.09 3530 1421 4.34 3746
6300 1315 4.15 3580
6600 —— —— — —— —— — —— —
6900 —— —— — —— —— — —— —
7200 —— —— — —— —— — —— —
7500 ——————————————
LEGEND
Bhp Brake Horsepower
FIOP Factory-Installed Option
Watts Input Watts to Motor
NOTES:
1. Standard low-medium static drive range is 891 to 1179 rpm. Alter-
nate high-static drive range is 1227 to 1550. Other rpms require a
field-supplied drive.
2. Maximum continuous bhp is 4.25 and the maximum continuous watts
are 3775. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
3. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Fan Performance table.
4. Interpolation is permissible. Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 8 for accessory/FIOP static pressure
information.
6. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confi-
dence. Using your fan motors up to the watts or bhp rating shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
7. Use of a field-supplied motor may affect wiring size. Contact your
Bryant representative for details.
—16—