Mitsubishi Electronics Q100UDEHCPU Sleep Apnea Machine User Manual


 
142
(b) "Auto Refresh Setting"
Set auto refresh target devices to communicate data by auto refresh using the multiple CPU high speed
transmission area. Up to 32 ranges can be set for each CPU module.
*1 Set the number of points within the points set for the "CPU Specific Send Range" of each CPU module.
*2 Bit devices can be specified in increments of 32 points (2 words).
*3 Set the device numbers for setting No.1 to No.32 so that they will not overlap.
Item Description Setting range
Points
Set the number of points for data communications
in increment of 2 points (word units).
• Setting range: 2 to 14336 points
*1
• Setting unit: 2 points
*2
Start
Specify the auto refresh target device.
For the host CPU module, specify the send target
device. For other CPU modules, specify the
receive target device.
• Device that can send data
*3
X, Y, M, L, B, D, W, R, ZR, SM, SD, SB, SW
• Device that can receive data:
*3
X, Y, M, L, B, D, W, R, ZR
• Leave this field blank if auto refresh is not executed. (The
field can be left blank only when it is used as a receive
target device.)