Table 3. TP972A Thermostat Specifications.*
Action
Supply Air Degrees
Old
Model No.
New
Model No.
Left
Bimetal
Right
Bimetal Setpoint
Pressure
psi (kPa)
Throttling
Range
Special Features
TP972A 1002 TP972A 2002 60-90°F 13 (Cooling) or Adjustable —
TP972A 1010 TP972A 2010 R.A. D.A. 15-30°C 18 (Heating) 2-10°F—
TP972A 1028 TP972A 2028 60-90°F (90 or 124) (1.1-5.6°C) Universal Modernization Kit with Universal
Window Cover
TP972A 1036 TP972A 2036 60-90°F
(Cooling)
Energy Conservation, Separate Setpoints
TP972A 1044 TP972A 2044 (50-75°F
(Heating)
Honeywell Thermostat Modernization Kit
with Universal Window Cover
TP972A 1051 No Replacement 78-90°F
(Cooling)
60-72°F
(Heating)
Separately
Adjustable
2-10°F
(1.1-5.6°C)
Limited Control Range (LCR)
TP972A 1077 No Replacement 75-90°F
(Cooling)
Setpoint Stop at 75F Minimum
TP972A 1085 No Replacement 50-75°F
(Heating)
16 (Cooling) or
21 (Heating)
(110 or 145)
TP972A 1093 No Replacement 78-90°F
(Cooling)
13 (Cooling) or
18 (Heating)
Limited Control Range (LCR)
TP972A 1101 No Replacement 60-72°F
(Heating)
(90 or 124) Universal Limited Control Range (LCR)
Modernization Kit
TP972A 1119 No Replacement 78-90°F
(Cooling)
13 (Cooling) or
18 (Heating)
Limited Control Range (LCR)
TP972A 1127 No Replacement 55-65°F
(Heating)
(90 or 124) Universal Limited Control Range (LCR)
Modernization Kit
TP972A 1143 TP972A 2143 D.A. R.A. 60-90°F 14 (Heating) or
19 (Cooling)
(97 or 131)
Separately
Adjustable
2-10°F
Specifically for replacing Johnson
Cooling/Heating Thermostats
TP972A 1150 TP972A 2150 R.A. D.A. 15-30°C Cooling
12-24 Heating
13 (Cooling) or
18 (Heating)
(90 or 124)
(1.1-5.6°C) Energy Conservation, Separate Setpoints
TP972A 1168 TP972A 2168 D.A. R.A. 60-90°F
(Cooling)
50-75°F
16 (Cooling) or
21 (Heating)
110 or 145)
TP972A 1176 TP972A 2176 D.A. R.A. (Heating) 20 (Cooling) or
25 (Heating)
(138 or 172)
TP972A 1184 TP972A 2184 13 (Cooling or
18 (Heating)
Includes 14004406-901 Cover, Separate
Setpoints
— TP972A 2192 R.A. D.A. 60-90°F (90 or 124) Includes Universal Window Cover
— TP972A 2200 D.A. R.A. 14 (Cooling) or
19 (Heating)
(97 or 131)
—
*All single-temperature, tw0-pipe, two-element, automatic changeover, and cooling/heating.