A SERVICE OF

logo

multiple servers
4 built-in communications ports (2-DB9, 2-USB) for remote monitoring and unattended shutdown
Slot for SNMP/web card (part#: SNMPWEBCARD) and environmental sensor (part#: ENVIROSENSE) for remote communications in large
IP environments
Supports Tripp Lite's WatchDog software application to restore unresponsive programs by automatically restarting them and rebooting
completely locked computers by automatically switching UPS power off and back on again
Communication ports support on battery, low battery, power restored, AC line voltage, DC battery voltage, load percentage, battery charge
current, battery capacity, internal UPS temperature and line frequency status messaging. Interface supports timed inverter shutoff after
unattended shutdown, activate self-test and 10 second reboot of connected equipment
3 individual customized load management receptacles can be individually powered off and back on again via software interface to reboot
remote equipment or shed less critical loads to extend battery runtime for the most critical equipment
Built-in Emergency Power Off (EPO) interface supports emergency shutoff in large facilities
Hot-swappable/user replaceable batteries allow on-site battery replacement through the front panel without powering off connected
equipment or removing the UPS from the rack
UPS battery set ships fully assembled and ready for use, no time consuming, connection of individual internal batteries by user is
necessary
UL (USA), cUL (Canada), NOM (Mexico), FCC Class A
$250,000 Ultimate Lifetime Insurance. No warranty cards required for coverage!
2 year manufacturers product warranty
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V AC
Frequency
compatibility
60 Hz
OUTPUT
Output VA 2200
Output watts 1600
Output nominal
voltage
120V AC
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-18% / +8%), BATTERY MODE: PWM sine wave output 120V +/-5%
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 7 NEMA 5-15R, 2 NEMA 5-20R and 1 NEMA L5-20R
Customized load
management
receptacles
"3 individually controllable outlets support load shedding and remote reboot on demand of locked network devices.
Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers
and other critical devices. "
Overload protection 20A input circuit breaker
INPUT
Maximum input amps 16A / 1840 watts
Input connection type NEMA 5-20P
Input cord length 8 ft., 12 gauge
Recommended
Electrical Service
20A 120V
BATTERY
Full load runtime 7 minutes (2200VA)
Half load runtime 19 minutes (1100VA)
Expandable battery
runtime
Runtime is expandable with BP48V24-2U (limit 1) or BP48V60RT3U (multi-pack compatible) external battery packs
DC system voltage 48 VDC