Full load runtime 4 minutes (3000VA)
Half load runtime 11 minutes (1500VA)
Expandable battery
runtime
Supports extended runtime with optional external battery packs BP48V242U (limit 1) and BP48V60RT3U (multi-pack
compatible)
DC system voltage 48V DC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge rate 6.5 hours
Replacement
Battery Cartridge
RBC94-2U
VOLTAGE REGULATION
Voltage regulation
description
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without
using battery power, during brownouts to 79V and overvoltages to 147V
Overvoltage
correction
Input voltages between 128 and 147V AC are reduced by 12%
Direct pass through Input voltages between 105 and 127V AC are passed on to connected equipment unchanged
Brownout correction Input voltages between 95 and 104V AC are boosted by 12%
Severe brownout
correction
Input voltages between 79 and 94V AC are boosted by 24%
LEDS ALARMS & SWITCHES
Front panel LEDs 5 front panel LEDs รข Green POWER LED, Green VOLTAGE CORRECTION LED, 3 color BATTERY CHARGE LED,
3 color OUTPUT LOAD LED, red BATTERY WARNING LED
Alarms 3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short
beeps) and low battery (continuous tone)
Switches Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
AC surge
suppression
480 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 72
Shipping weight (kg) 32.7
Shipping
Dimensions
(HWD/in)
9 x 23.5 x 20
Shipping
Dimensions
(HWD/cm)
22.9 x 59.7 x 50.8
Unit weight (lbs) 64
Unit weight (kg) 29.1
Unit Dimensions
(HWD/in)
3.5 x 17.5 x 19
Unit Dimensions
(HWD/cm)
8.89 x 44.5 x 48.3
Material of
construction
Steel