Set the switch to UPS during normal operation and connected equipment will receive full-time conditioned power from the UPS
Set the switch to Utility to bypass the UPS and provide connected equipment with unfiltered power directly from the Utility line cord while the
UPS system is removed and replaced with a fresh one
Once the new UPS is up and running with all connections restored, set the switch back to the UPS setting to once again provide
fully-conditioned UPS power to connected equipment
Specifications
OVERVIEW
PDU Type Hot-Swap
OUTPUT
Output Watt Capacity
(watts)
2300
Output Capacity Details 2.1kW (208V input), 2.2kW (220V input), 2.3kW (230V input), 2.4kW (240V input), 2.0kW (200V input); 10A
maximum
Frequency compatibility 50 / 60 Hz
Output nominal voltage 200-240V nominal, single phase
Outlet quantity / type 8 C13 outlets support critical connected loads; 1 designated pass-through C13 outlet supports C14 input plug
from UPS
Outlet Type IEC-C13
INPUT
PDU Input Voltage 200; 208; 220; 230; 240
Maximum Input Amps
(A)
10
Input connection type UTILITY & UPS inputs are available from separately labelled C14 inlets, compatible with included C13-C14
interconnect cables or with compatible user-supplied cabling
PDU Plug Type IEC-320 C14
Input cord length (ft.) 6
Input cord length (m) 1.83
Phase Single-Phase
LEDS ALARMS & SWITCHES
Switches Manual 2 position transfer switch offers fast switching between UPS and Utility operating modes in less than 6
milliseconds
Front panel LEDs Lighted indicators confirm UPS and Utility switch position and operating mode
PHYSICAL
Shipping Dimensions
(HWD/in)
9.84 x 22.75 x 9.44
Shipping Dimensions
(HWD/cm)
25 x 57.8 x 24
Shipping weight (lbs) 11
Shipping weight (kg) 5
Unit Dimensions
(HWD/in)
3.42 x 17.32 x 3.03